EasyManua.ls Logo

Fronius IG 4000 - Field Adjustable Trip Points

Fronius IG 4000
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
107
EN-US
Field adjustable
trip points
Relevant stan-
dards and direc-
tives
Field adjustable trip points 208 V 240 V
Nominal AC output voltage,
Line-to-Line, [V]
208 240
Operating AC voltage range default,
Line-to-Line, [V]
183-229 212-264
Adjustment range for voltage,
Line-to-Line, [V]
180-240 180-270
Voltage trip limit accuracy
Line-to-Line,
[% of nominal value]
± 1,5 ± 1,5
Nominal output frequency [Hz] 60 60
Operating frequency range [Hz] 59.3-60.5 59.3-60.5
Adjustment range for frequency [Hz] 57.0-60.5 57.0-60.5
Frequency trip limit accuracy, [Hz] ± 0,02 ± 0,02
Reconnect time, [s] 305 305
Adjustment range for reconnect time, [s] 1-999 1-999
Operating AC voltage range
Line-to-Neutral, [V]
106 - 132 106 - 132
Adjustment range for voltage
Line-to-Neutral, [V]
60 - 144 60 - 144
Voltage trip limit accuracy
Line-to-Neutral,
[% of nominal value]
± 1,5 ± 1,5
- UL 1741
- IEEE 1547
- IEEE 1547.1
- ANSI/IEEE C62.41
- FCC Part 15 A & B
- NEC Article 690
- C22. 2 No. 107.1-01
(September 2001)

Table of Contents