EasyManuals Logo

Fronius Symo 7.0-3-M Installation Instructions

Fronius Symo 7.0-3-M
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
17
EN
If overlength AC or DC cables are to be laid
in loops in the connection area, attach the
cables with cable ties to the eyelets provi-
ded on the top and bottom of the connecti-
on block.
Maximum fuse
rating on alternat-
ing current side
max. C 25 A
AC ~
Inverter Phases AC power Maximum
fuse rating
Recommend-
ed fuse rating
Fronius Symo 3.0-3-S / -M 3 3000 W C 25 A C 10 A
Fronius Symo 3.7-3-S / -M 3 3700 W C 25 A C 13 A
Fronius Symo 4.5-3-S / -M 3 4500 W C 25 A C 16 A
Fronius Symo 5.0-3-M 3 5000 W C 25 A C 16 A
Fronius Symo 6.0-3-M 3 6000 W C 25 A C 16 A
Fronius Symo 7.0-3-M 3 7000 W C 25 A C 20 A
Fronius Symo 8.2-3-M 3 8200 W C 25 A C 25 A

Table of Contents

Other manuals for Fronius Symo 7.0-3-M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Symo 7.0-3-M and is the answer not in the manual?

Fronius Symo 7.0-3-M Specifications

General IconGeneral
AC nominal output7.0 kW
Max. input voltage1000 V
MPP voltage range200 - 800 V
Number of MPP trackers2
Protection classIP65
AC nominal voltage400 V
Frequency50 / 60 Hz
THD< 3%
Operating Temperature Range-25°C to +60°C
Warranty5 years
Max. apparent AC power7.0 kVA
Efficiency98.0%