Pump Control Quick Guide
19
The following table (Table 2.1), “Common parameters to all the pump control systems”, shows the
common parameters to all of the control systems using
inverter. These are known as the
basic parameters.
In addition to the following table, there is also a specific parameters table.
If you are adjusting the inverter by means of the TP-E1 keypad, it is recommended to set E52 to “2”, in
order to be able to access to all of the inverter’s menus.
Note: The following values are shown as an example and may not necessarily work in your application
Table 2.1: Common parameters to all pump control systems
CONDITIONS TO AHCIEVE GOOD CONTROL INA A MONO-REGULATED PUMP
The code values should meet the following conditions in order to achieve stable operational behaviour.
Condition for sleeping/wake-up frequencies
Condition for frequencies where auxiliary pumps are connected/disconnected
The function codes J34, J36 and J94 belong to specific function codes group and will be explained below.
Common parameters to all of the pump control systems
Name Default setting Example’s Value User’s Value
F02 RUN command 2 1
F07 Acceleration time 1 20.00 s 3.00 s
F08 Deceleration time 1 20.00 s 3.00 s
F11 Electronic Thermal Overload protection. Overload detection Level
100% of the motor rated
current
13.0 A
F12 Electronic Thermal Overload protection. Time constant
5.0 min
(22kW or
below)
10.0 min
(30kW or
above)
5 min
F15 Frequency Limiter. High 70.0 Hz 50.0 Hz
F16 Frequency Limiter. Low 0.0 Hz 25.0 Hz
F26 Motor Sound. Carrier Frequency 15 kHz 3 kHz
E40 PID display coefficient A + 100.00 Transducer’s pressure
E43 LED display. Function 0 12
E62 Analog input for terminal C1(Extension function selection) 0 5
P01 Motor. Number of poles 4 4
P02 Motor. Rated Capacity
Rated capacity of standard
motor
5.5 kW
P03 Motor. Rated Current
Rated current of standard
motor
13.0 A
H91 C1 signal disconnection detection 0.0 s 0.5 s
J01 PID Control. Mode selection 0 1
J03 PID Control. Gain P 0.100 2.500
J04 PID Control. Integral time I 0.0 s 0.2
J15 PID Control. Sleep frequency 0 Hz 35.0 Hz
J16 PID Control. Sleep frequency level latency 30 s 15 s
J17 PID Control. Wake-up frequency 0 Hz 38.0 Hz
J18 PID Control. Upper limit of PID process output 999 50.0 Hz
J19 PID Control. Lower limit of PID process output 999 25.0 Hz
J23 PID Control. Starting From the Slow Flow rate Stop (Dev. Level) 0 % 5 %
J24 PID Control. Starting From the Slow Flow rate Stop (Latency) 0 sec 1 sec