Pump Control Quick Guide
25
Condition for frequencies where auxiliary pumps are connected/disconnected
Condition for the connection of the additional pump
Using this control topology, it can be necessary to delay the disconnection of the motor from the
commercial power supply (J37), in order to prevent the simultaneous disconnection of the auxiliary and
the additional pumps. That is, the first pump to be disconnected should be the additional pump and then
the auxiliary pump, but never at the same time.
The following table (Table 3.2) shows the specific function codes to successfully control a mono-regulated
pump control system with 1 regulated pump + 4 auxiliary pumps + 1 additional pump:
Table 3.2: Specific function codes for Mono-regulated pump control with 1 regulated pump + 4 auxiliary
pumps + 1 additional pump
Note:
The default setting for function code J93 and J94 (0 Hz) may work properly in your installation
without adjusting it to the suggested value (40 Hz and 39 Hz respectively).
Specific Function Codes for mono-regulated pump control with 1 regulated pump + 4 auxiliary pumps + 1 additional
Name Default Setting Example’s value User’s value
E20 Status Signal Assignment to Y1 0 65 (M3_L)
E21 Status Signal Assignment to Y2 1 67 (M4_L)
E22 Status Signal Assignment to Y3 2 2 (FDT)
E24 Status Signal Assignment to Y5A/C 10 61 (M1_L)
E27 Status Signal Assignment to 30A/B/C 99 63 (M2_L)
E31 Frequency Detection (FDT). Level 50.0 Hz 47.0 Hz
E32 Frequency Detection (FDT). Hysteresis 1.0 Hz 8.0 Hz
J25 Pump Control. Mode Selection 0 1
J26 Motor 1 mode 0 1
J27 Motor 2 mode 0 1
J28 Motor 3 mode 0 1
J29 Motor 4 mode 0 1
J34 Start of commercial power-driven motor. Frequency 999 48 Hz
J35 Start of commercial power-driven motor. Duration 0.00 s 5.00 s
J36 Stop of commercial power-driven motor. Frequency 999 30 Hz
J37 Stop of commercial power-driven motor. Duration 0.00 s 1.00 s
J41 Motor Unmount switching Level 0 % 50 %
J44 Motor Mount switching Level 0 % 50 %
J93 PID Start Frequency (Mount) 0 Hz 40 Hz
J94 PID Start Frequency (Unmount) 0 Hz 38 Hz