Pump Control Quick Guide
   
30
 
 
 
The  following  is  an  explanation  of  the  requirements  or  conditions  to  connect  a  regulated 
pump to the commercial power supply, and to disconnect a pump from the commercial power 
supply: 
 
• Connection of a regulated pump to the main supply 
 
 
 
If the regulated pump’s output frequency rises above the level stored in J34 during the time established in 
J35, the inverter will understand that the regulated pump is not enough to maintain the required pressure 
and will get ready to connect the pump to the commercial power supply.  
 
 
 
If the condition above is  accomplished,  the inverter will connect  the regulated  pump to  the commercial 
power supply and will take another pump of the system as a regulated one.  
 
 
 
 
Figure 4.4: Connection of a regulated pump to the commercial power supply. 
 
 
•  Disconnection of a pump from the main supply 
 
 
 
 
If  the  regulated  pump’s  output  frequency  decreases  under  the  level  established  in  function  code  J36 
during the time J37, the inverter will understand that is not necessary to keep a pump connected to the 
commercial power supply and will get ready for its disconnection. 
 
 
 
If the condition above is accomplished, the inverter will increase the regulated pump’s output frequency 
until the frequency stored in J94 using the acceleration time in J40. Once the frequency level achieves this, 
the PID control will be activated.  
 
This behaviour can be useful to reduce the possible sudden pressure fluctuations that may occur when a 
pump is disconnected from the commercial power supply.