Pump Control Quick Guide
33
The following table (table 4.2) shows the specific function codes for multi-regulated pump control system
with 2/3 regulated pumps:
Table 4.2: Specific parameters for Multi-regulated pump control with 2/3 regulated pumps
Note:
The default setting for function code J94 (0 Hz) may work properly in your installation without
adjusting it to the suggested value (39 Hz).
DESCRIPTION OF SPECIFIC PARAMETERS OF MULTI-REGULATED PUMP CONTROL WITH
2/3 REGULATED PUMPS
PID and pump control
J25: Pump control. Mode selection
The function code J25 defines which type of pump control is going to be used
J25 = 0 Pump control disabled
J25 = 1 Mono-regulated pump control enabled
J25 = 2 Multi-regulated control enabled
J26, J27, J28: Motor 1 mode, Motor 2 mode, Motor 3 mode
The function codes J26, J27, J28 define:
J26 = 0 pump 1 unavailable
J26 = 1 pump 1 available
J26 = 2 pump 1 connected to the commercial power supply
J27= 0 pump 2 unavailable
J27 = 1 pump 2 available
J27 = 2 pump 2 connected to the commercial power supply
J28 = 0 pump 3 unavailable
J28 = 1 pump 3 available
J28 = 2 pump 3 connected to the commercial power supply
In normal operation, the mode to be used is 1.
Specific Parameters for Multi-regulated pump control with 2 / 3 regulated pumps
Name Default value
For 2 regulated pumps
(without OPC-F1-RY)
For 3 regulated pumps
(with OPC-F1-RY)
User’s Value
E20 Status Signal Assignment to Y1 0 63 (M2_L) 64 (M3_I)
E21 Status Signal Assignment to Y2 1 62 (M2_I) 1
E24 Status Signal Assignment to Y5A/C 10 61 (M1_L) 61 (M1_L)
E27 Status Signal Assignment to 30A/B/C 99 60 (M1_I) 60 (M1_I)
J25 Pump Control. Mode Selection 0 2 2
J26 Motor 1 Mode 0 1 1
J27 Motor 2 Mode 0 1 1
J28 Motor 3 Mode 0 0 1
J34 Start of commercial power-driven motor.Frequency 999 48 Hz 48 Hz
J35 Start of commercial power-driven motor.Duration 0.00 s 5.00 s 5.00 s
J36 Stop of commercial power-driven motor.Frequency 999 30 Hz 30 Hz
J37 Stop of commercial power-driven motor.Duration 0.00 s 1.00 s 1.00 s
J41 Motor Unmount switching level 0 % 50 % 50 %
J45 Status Signal Assignment to Y1A/B/C 100 100 63 (M2_L)
J46 Status Signal Assignment to Y2A/B/C 100 100 62 (M2_I)
J47 Status Signal Assignment to Y3A/B/C 100 100 65 (M3_L)
J94 PID Start Frequency (Unmount) 0 Hz 39 Hz 39 Hz