Pump Control Quick Guide
9
The following table (table 1.1), called “Common parameters to the all pump control systems”, shows the
common parameters to all pump control systems using , these are known as the basic
parameters.
In other chapters, Specific Parameters’ table will be shown. These parameters will depend on the chosen
control system.
If you are adjusting the inverter by means of the TP-E1 keypad, is recommended to set E52 to “2”, in
order to be able to access to all the inverter menus.
Note: The following values are shown as an example and could not work properly in your application.
Table 1.1: Common parameters to all pump control systems
CONDITIONS TO ACHIEVE GOOD CONTROL IN A SINGLE PUMP
If it’s necessary to use a different parameter set-up to that shown in the above “Example Values” column,
please bear in mind the following condition:
Sleeping/ Wake-up frequency Condition
Common Parameters to all pump control systems
Name Default setting Example’s Value User’s Value
F02 Run command 2 1
F07 Acceleration Time 1 20.00 s 3.00 s
F08 Deceleration Time 1 20.00 s 3.00 s
F11 Electronic Thermal Overload protection. Overload detection Level
100% of the motor rated
current
13.0 A
F12 Electronic Thermal Overload protection. Time constant
5.0 min
(22kW or
below)
10.0 min
(30kW or
above)
5 min
F15 Frequency Limiter. High 70.0 Hz 50.0 Hz
F16 Frequency Limiter. Low 0.0 Hz 25.0 Hz
F26 Motor Sound. Carrier Frequency 15 kHz 3 kHz
E40 PID Display coefficient A + 100.00 Transducer’s pressure
E43 LED monitor. Item selection 0 12
E62 Analog Input for [C1] 0 5
P01 Motor. Number of Poles 4 4
P02 Motor. Rated capacity
Rated Capacity Standard
Motor
5.5 kW
P03 Motor. Rated current
Rated Current Standard
Motor
13.0 A
H91 C1 signal disconnection detection 0.0 s 0.5 s
J01 PID Control. Mode Selection 0 1
J03 PID Control. Gain P 0.100 2.500
J04 PID Control. Gain I 0.0 s 0.2
J15 PID Control. Stop frequency for slow flow rate 0 Hz 35.0 Hz
J16 PID Control. Slow flow rate level stop latency 30 s 15 s
J17 PID Control. Starting Frequency 0 Hz 38.0 Hz
J18 PID Control. Upper limit of process output 999 50.0 Hz
J19 PID Control. Lower limit of process output 999 25.0 Hz
J23 PID Control. Starting From the Slow Flow rate Stop (Dev. Level) 0 % 5 %
J24 PID Control. Starting From the Slow Flow rate Stop (Latency) 0 sec 1 sec