50
Parameter functions and setting procedure
When alarm action code is changed, alarm set value may also become different
from previous settings.
Power-cycle the controller after you change the alarm type.
[Setting example]
Setting the type of the alarm 1 to “upper limit deviation alarm with hold” ––––––––
Display Operating procedure
1.
Press and hold the key for about three seconds during the SV/PV display.
appears.
2.
Press the key to display .
3.
Press the key.
The setpoint starts blinking.
4.
Press the , or keys to change “ 0 ” to “ 8 .”
5.
Press the key or wait for three seconds to save the change.
6.
Press the key.
The screen returns to the SV/PV display.