25
Specification
Power voltage: 100 (- 15%) to 240 VAC (+10%), 50/60Hz
or 24VDC/24 VAC (±10%), 50/60Hz
Power consumption: 15VAC or less/240VAC
Sensor input: Thermocouple, 3-wire resistance bulb,
1 to 5VDC
Control method: PID or fuzzy PID or ON/OFF (two positions)
Relay output: 1C contact, 220 VAC/30 VDC 3A (resistive load)
mechanical life ; 10 million times or over (no load)
electrical life ; 100 thousands times or over (rating load)
SSR/SSC driving output: ON: 15 to 30 VDC
(voltage pulse output) OFF: 0.5VDC or less
maximum current ; 60mA or less
2 point alarm for PXW4: 25mA or less
SSR/SSC driving output for control outputs 1 and 2: 60mA or
less in total
DC4-20mA output: Allowable load resistor 600 or less
Alarm output: Relay contact (1a contact) 220 VAC/30 VDC 1A (resistive load)
Heater disconnection alarm output: Relay contact (1a contact) 220 VAC/30 VDC 1A (resistive load)
Operating ambient temperature: -10 to 50°C
Operating ambient humidity: 90%RH or less (no condensation)
Preservation temperature: -20 to 60°C
Operating environmental condition: Installation category II, contamination degree 2
Warm-up time: 30 minutes or more