28
Example) Altering alarm hysteresis 1°C to 3°C
Key operation Description
Press the SEL key for 3 seconds,
and P-n1 is displayed.
Press the SEL key repeatedly until
P-An is displayed.
Press the or key to display
3.
Press the DATA key. Current data
is displayed.
Press the SV key when you need to
display the operation status display.
After pressing the ENT key, the data
is registered.
Display
SEL
SEL
ENT
SV
DATA
Alarm hysteresis width (option) (Setting range: 0 to 50%FS)
[Description]
Alarm is 2-position action, ON and
OFF, while hysteresis is the differ-
ence in input ON and OFF. For ex-
ample, when hysteresis is 5°C, the
width of ON and OFF is 5°C.
Normally, it is set to 1°C
Decimal point is given automatically
by setting it with P-dP.
Related parameter: AL (Page 9)
AH (Page 10)
P-AH (Page 30)
P-AL (Page 30)
ON
ON5°C
5°C
5°C
5°C
Input
Input
ON
OFF
OFF
OFF
(Upper limit alarm)
(Lower limit alarm)
(Range alarm)
OFF
AL
AH
AL AH