31
Upper limit alarm (ALM1) and lower limit alarm (ALM2) are the same key operation with the exception of range alarm action.
Upper limit alarm (ALM1) can be used low-low limit alarm by setting is as lower limit alarm or lower limit alarm (ALM2) as
upper-upper alarm by setting is as upper limit alarm.
Example) Altering upper limit alarm (ALM1) action from
upper limit deviation alarm to upper limit ab-
solute value alarm
Key operation Description
Press the SEL key for 3 seconds,
and P-n1 is displayed.
Press the SEL key repeatedly until
P-AH is displayed.
Press the or key to display
1.
Press the DATA key. Data is
displayed.
Display 5 due to deviation alarm.
Check that 5 is displayed and change
the alarm to absolute value alarm 1.
Press the SV key when you need to
display the operation status display.
After pressing the ENT key, the data
is registered.
Display
SEL
SEL
SV
DATA
ENT