Limit of maximum speed based on outdoor temperature
A zone
B zone
C zone
D zone
E zone
F zone
Outdoor
temperature drops
Outdoor
temperature rises
93.2°F
(34°C)
96.8°F
(36°C)
86.0°F
(30°C)
66.2°F
(19°C)
50.0°F
(10°C)
32.0°F
(0°C)
89.6°F
(32°C)
69.8°F
(21°C)
53.6°F
(12°C)
35.6°F
(2°C)
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH MED LOW QUIET
ABUH18LUAS
A zone 102 46 36 26
B zone 102 46 36 26
C zone 58 36 32 26
D zone 39 32 30 20
E zone 39 32 30 20
F zone 39 32 30 20
ABUH24LUAS
A zone 102 61 50 34
B zone 102 61 50 34
C zone 68 50 39 34
D zone 57 39 34 32
E zone 57 39 34 32
F zone 57 39 34 32
ABUH30LUAS
A zone 98 58 49 42
B zone 98 58 49 42
C zone 67 51 46 40
D zone 51 42 37 32
E zone 51 42 37 32
F zone 51 42 37 32
ABUH36LUAS
A zone 103 79 69 46
B zone 103 79 69 46
C zone 96 69 55 46
D zone 69 55 46 40
E zone 69 55 46 40
F zone 69 55 46 40