EasyManua.ls Logo

Fujitsu ABUH18LUAS - Heating Operation

Fujitsu ABUH18LUAS
226 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
If the room temperature is 11°F (6.0°C) lower than a set temperature, the operation rotation num-
ber of compressor will attain to maximum performance.
If the room temperature is 2°F (1.0°C) higher than a set temperature, the compressor will be
stopped.
→hen the room temperature is within the range of +2°F (1.0°C) to -11°F (6.0°C) of the setting tem-
perature, the rotation number of compressor is controlled within the range shown below.
Rotation number range of compressor
Unit: rps
Model name Minimum frequency Maximum frequency
ABUH18LUAS 8 130
ABUH24LUAS 10 130
ABUH30LUAS 15 110
ABUH36LUAS 15 120
1-2. Heating operation - (04-3) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents