Setting the Cooler Room Temperature Correction
Depending on the installed environment, the room tempera-•
ture sensor may require a correction. The settings may be
selected as shown in the table below. (The unit is factory-set
to “00”.)
Setting Description Function Number Setting Value
Standard
30
00
Lower control 01
Setting the Heater Room Temperature Correction
Depending on the installed environment, the room tempera-•
ture sensor may require a correction. The settings may be
changed as shown in the table below. (The unit is factory-
set to “00”.)
Setting Description Function Number Setting Value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
Setting Other Functions
The following settings are also possible, depending on the •
operating conditions. (The unit is factory-set to “00”.)
Auto Restart
Setting Description Function Number Setting Value
Yes
40
00
No 01
Indoor Room Temperature Sensor Switching Function
(Wired remote controller only)
Setting Description Function Number Setting Value
No
42
00
Yes 01
If setting value is “00”, room temperature is controlled by the •
indoor unit temperature sensor.
If setting value is “01”, room temperature is controlled by •
either indoor unit temperature sensor or remote control unit
sensor.
Setting record
Record any changes to the settings in the following table.•
Setting Setting Value
Ceiling height
Filter sign
Cooler room temperature
correction
Heater room temperature
correction
Auto restart
Indoor room temperature
sensor switching function
After completing the FUNCTION SETTING, be sure to turn off
the power and turn it on again.
8.2. Function setting
STEP 2
Selecting the Function Number and Setting Value
Press the SET TEMP. ((1) ) ( ) buttons to select the func-
tion number. (Press the MODE button to switch between
the left and right digits.)
Press the FAN button to proceed to setting the value. (2)
(Press the FAN button again to return to the function
number selection.)
Press the SET TEMP. ((3)
) ( ) buttons to select the set-
ting value. (Press the MODE button to switch between the
left and right digits.)
Press the TIMER MODE button, and START/STOP button, (4)
intheorderlistedtoconrmthesettings.
Press the RESET button to cancel the function setting (5)
mode.
After completing the FUNCTION SETTING, be sure to turn (6)
off the power and turn it on again.
CAUTION
After turning off the power, wait 10 seconds or more before •
turning on it again. The FUNCTION SETTING doesn’t
become effective if it doesn’t do so.
Setting the Ceiling Height
Select the setting values in the table below according to the •
height of the ceiling. (The unit is factory-set to “00”.)
Setting Description [m] Function Number Setting Value
Standard
(2.5 to 3.0)
20
00
High ceiling
(3.0 to or more)
01
Setting the Filter Sign
The indoor unit has a sign to inform the user that it is time to •
cleanthelter.
Selectthetimesettingfortheltersigndisplayintervalinthe•
table below according to the amount of dust or debris in the
room. (The unit is factory-set to “00”.)
Ifyoudonotwishtheltersigntobedisplayed,selectthe•
setting value for “No indication”.
Setting Description
[hours]
Function Number Setting Value
Standard
(2,500)
11
00
Long interval
(4,400)
01
Short interval
(1,250)
02
No indication 03