EasyManuals Logo

Fujitsu AO G12KATA Series Service Instruction

Fujitsu AO G12KATA Series
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
1-3. Dry operation
The compressor rotation frequency shall change according to the temperature, set temperature, and
room temperature variation which the room temperature sensor of the indoor unit has detected as
shown in the table below.
Zone is defined by set temperature and room temperature.
Compressor frequency range
Unit: rps
Model name Outdoor temperature zone Operating frequency
AUXG09KVLA
X zone 41
J zone 41
Y zone 0
AUXG12KVLA
X zone 54
J zone 54
Y zone 0
AUXG14KVLA
X zone 43
J zone 43
Y zone 0
AUXG18KVLA
X zone 39
J zone 39
Y zone 0
AUXG22KVLA
X zone 36
J zone 36
Y zone 0
Compressor control based on room temperature
Ts+0.5°C
Ts -1.5°C
Ts-0.5°C
Ts+1.5°C
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
1-3. Dry operation - (04-5) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Other manuals for Fujitsu AO G12KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G12KATA Series and is the answer not in the manual?

Fujitsu AO G12KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G12KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals