8-1. External input
“Operation/Stop” mode can be selected with function setting of indoor unit.
A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
The wire connection should be separate from the power cable line.
¢
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
1
2

Terminal
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
¢
External input and output PCB
The indoor unit Operation/Stop can be set by using the input terminal on the PCB.
Input select
Use either one of these types of terminals according to the application. (Both types of terminals
cannot be used simultaneously.)
Dry contact
In case of internal power supply, set the slide switch of SW1 to "NON VOL" side.
1
2
C
Input 1 Input 2
PCB
Connected unit

+
+
-
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
Apply voltage
In case of external power supply, set the slide switch of SW1 to "VOL" side.
1
2
C
Input 1 Input 2 Power supply
PCB
Connected unit


+-
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
*2: Make the power supply DC 12 V to 24 V 10 mA or more.
- 38 -
8-1. External input
8. External input and output
CASSETTE TYPE
AUXG24-54KRLB
CASSETTE TYPE
AUXG24-54KRLB

Table of Contents

Other manuals for Fujitsu AOG30KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOG30KATA Series and is the answer not in the manual?

Fujitsu AOG30KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAOG30KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals