2) Ceiling height
Select the appropriate ceiling height according to the place of installation.
Function number Setting value Setting description Factory setting
20
00 Standard ♦
01 High ceiling
02 Low ceiling
For the specific height for each setting value, refer to “Installation space” in Chapter 2. "Dimensions"
on page 5.
In case of cassette type models:
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet
mode.
3) Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
Function number Setting value Setting description Factory setting
22
00 4-way ♦
01 3-way
4) Vertical airflow direction range control
To prevent draft, change the setting to "Upward" (01).
Note that the airflow in certain usage conditions may leave the ceiling dirty. In such cases, the use of
the optional Panel spacer is recommended.
Function number Setting value Setting description Factory setting
23
00 Standard ♦
01 Upward
Ceiling
Swing scope (standard)
Swing scope (upward)
- 51 -
9-2. Function settings by using remote controller
9. Function settings
CASSETTE TYPE
AUXG24-54KRLB
CASSETTE TYPE
AUXG24-54KRLB