1-28. LOW NOISE OPERATION
1-29. PEAK CUT OPERATION
01-33
(Table 16 : Outline of PEAK CUT OPERATION)
Low Noise Mode
MODE1
MODE2
Cooling
Heating
Cooling
Heating
Upper fan
Lower fan
Upper fan
Lower fan
Upper fan
Lower fan
Upper fan
Lower fan
520
520
520
520
520
520
520
520
40
46
29
36
52
52
32
37
57
55
36
38
58
58
37
39
Outdoor Fan Speed
( rpm )
Compressor Frequency ( rps )
AO *G36LATT AO *G45LATT AO *G54LATT AOTG60LATT
MODE1 MODE2 MODE3 MODE4
100%75%50%
0%
Forced thermostat-OFF
*The performance drops when operating in the LOW NOISE OPERATION.
The Current Value is limited to reduce the power consumption by External Input.
During the PEAK CUT OPERATION,
"CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION" and "LOW NOISE OPERATION" are effective,
and the outdoor unit operates by lowest current of them.
However, this function becomes invalid during DEFROST OPERATION.
*Percentage is rated electrical power ratio
The compressor frequency and the outdoor unit fan speed are limited to reduce the operation noise by External Input.
During the LOW NOISE OPERATION,
"CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION" and "PEAK CUT OPERATION" are effective,
and the outdoor unit operates by lowest current of them.
However, during the DEFROST OPERATION, the compressor operates by the frequency for DEFROST OPERATION.
( Table 15 : Detail of LOW NOISE OPERATION)