SERVICE PARTS INFORMATION 1
MPa
Compressor
Diagnosis method of Compressor (If outdoor unit LED displays error, refer to Trouble shooting )
Does not start up
Is there open or loose connection
cable?
Check connection of Compressor,
and winding resistance.
(Refer to the next page).
Check Inverter PCB connection of Compressor,
and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor can be
considered.
(Compression part broken or valve defective.)
>> If there is no failure, the defect of
Compressor is considered (Locked
compressor due to clogged dirt or
less oil)
Replace Compressor
Replace Compressor
Replace Compressor
Stops soon after starting up
Is there open or loose connection
cable?
Is Gas pipe valve open?
(Low Pressure is too low)
Check if Refrigerant is leaking.
(Recharge Refrigerant)
Check if Strainer is clogged.
(PARTS INFORMATION 3)
Abnormal noise
Defective Compressor
can be considered.
(due to inside dirt clogging
or broken component)
Check if vibration noise by
loose bolt or contact noise
of piping is happening.
02-39
2-4 SERVICE PARTS INFORMATION
MPa

Table of Contents

Other manuals for Fujitsu AOTG60LATT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOTG60LATT and is the answer not in the manual?

Fujitsu AOTG60LATT Specifications

General IconGeneral
BrandFujitsu
ModelAOTG60LATT
CategoryAir Conditioner
LanguageEnglish

Related product manuals