Type
Duct
Inverter heat pump
Model name ARU18RGLX ARU24RGLX ARU30RGLX
Power supply 208/230 V ~ 60 Hz
Power supply intake Outdoor unit
Available voltage range 187—253 V
Capacity
Cooling
Rated
kW 5.28 7.03 8.79
Btu/h 18,000 24,000 30,000
Min.—Max.
kW 1.58—6.30 1.58—8.5 2.81—10.26
Btu/h 5,400—21,500 5,400—29,000 9,600—35,000
Heating
47 °FDB
(Outdoor temp.)
Rated
kW 6.15 7.91 9.38
Btu/h 21,000 27,000 32,000
Min.—Max.
kW 1.58—7.5 1.58—9.5 2.7—11.43
Btu/h 5,400—25,600 5,400—32,400 9,200—39,000
17 °FDB
(Outdoor temp.)
Rated
kW 4.76 6.07 7.25
Btu/h 16,200 20,700 24,700
Max.
kW 5.81 7.29 8.83
Btu/h 19,800 24,800 30,100
Input power
Cooling
Rated
kW
1.38 1.90 2.83
Min.—Max. 0.53—2.08 0.63—2.82 0.70—3.43
Heating
47 °FDB
(Outdoor temp.)
Rated 1.50 2.06 2.48
Min.—Max. 0.51—2.19 0.54—2.96 0.62—3.27
17 °FDB
(Outdoor temp.)
Rated 1.49 2.36 2.53
Max. 2.17 3.39 3.33
Fan
HIGH
W
53 84 139
MED 30 44 79
LOW 22 27 58
QUIET 15 15 46
Current
Cooling
Rated A
6.1 8.3 12.4
Heating 6.6 9.0 10.9
EER Cooling
kW/kW 3.81 3.69 3.11
Btu/hW 13.0 12.6 10.6
COP Heating
kW/kW 4.10 3.84 3.78
Btu/hW 14.0 13.1 12.9
SEER Cooling
Btu/hW
19.0 17.5 16.5
HSPF Heating 10.9 10.8 10.4
Power factor
Cooling
%
98.4 99.5 99.2
Heating 98.8 99.5 98.9
Moisture removal pints/h (L/h) 3.8 (1.8) 4.0 (1.9) 5.1 (2.4)
Maximum operating current *
1
Cooling
A
13.6 15.6 15.6
Heating 14.1 16.1 16.1
Fan
Airflow rate
Cooling
HIGH
CFM (m
3
/h)
618 (1,050) 800 (1,360) 1,001(1,700)
MED 494 (840) 636 (1,080) 800 (1,360)
LOW 430 (730) 518 (880) 700 (1,190)
QUIET 371 (630) 400 (680) 630 (1,070)
Heating
HIGH 618 (1,050) 800 (1,360) 1,001(1,700)
MED 494 (840) 636 (1,080) 800 (1,360)
LOW 430 (730) 518 (880) 700 (1,190)
QUIET 371 (630) 400 (680) 630 (1,070)
Type × Q'ty Sirocco fan × 2
Motor output W 197 375
Static pressure range Pa 30 to 200
Sound pressure level *
2
Cooling
HIGH
dB (A)
31 35 38
MED 28 30 34
LOW 25 28 30
QUIET 24 24 29
Heating
HIGH 31 35 38
MED 28 30 34
LOW 25 28 30
QUIET 24 24 29
Heat exchanger type
Dimensions (H × W × D) in (mm) 16-9/16 × 29-13/16 × 1-9/16 (420 × 758 × 39.9)
Fin pitch FPI 18
Rows × Stages 3 × 20
Pipe type Copper
Fin type
Aluminum
Hydrophilic coating
Enclosure
Material Steel
Color
Dimensions
(H × W × D)
Net
in (mm)
11-13/16 × 39-3/8 × 27-9/16 (300 × 1,000 × 700)
Gross 15-3/4 × 48-3/4 × 34-7/16 (400 × 1,238 × 875)
Weight
Net
lb (kg)
93 (42)
Gross 110 (50)
Connection pipe
Size
Liquid
in (mm)
Ø 1/4 (Ø 6.35) Ø 3/8 (Ø 9.52)
Gas Ø 1/2 (Ø 12.7) Ø 5/8 (Ø 15.88)
Method Flare
Drain hose
Material PVC
Size in (mm) Ø 13/16 (20.7) [I.D.], Ø 1-1/16 (26.6) [O.D.] (VP25)
Operation range
Cooling
°F (°C) 64.4 to 89.6 (18 to 32)
%RH 80 or less
Heating °F (°C) 60.8 to 86.0 (16 to 30)
- 4 -
1. Specifications
DUCT TYPE
ARU12-48RGLX
DUCT TYPE
ARU12-48RGLX

Table of Contents

Other manuals for Fujitsu AOU24RGLX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU24RGLX and is the answer not in the manual?

Fujitsu AOU24RGLX Specifications

General IconGeneral
BrandFujitsu
ModelAOU24RGLX
CategoryAir Conditioner
LanguageEnglish

Related product manuals