Duct
Inverter heat pump
Model name ARU36RGLX ARU42RGLX ARU48RGLX
Power supply 208/230 V ~ 60 Hz
Power supply intake Outdoor unit
Available voltage range 187—253 V
Capacity
Cooling
Rated
kW 10.55 12.31 14.07
Btu/h 36,000 42,000 48,000
Min.—Max.
kW 2.81—11.43 5.01—13.19 5.01—14.65
Btu/h 9,600—39,000 17,100—45,000 17,100—50,000
Heating
47 °FDB
(Outdoor temp.)
Rated
kW 10.55 13.77 15.50
Btu/h 36,000 47,000 53,000
Min.—Max.
kW 2.7—14.07 5.28—14.95 5.28—16.12
Btu/h 9,200—48,000 18,000—51,000 18,000—55,000
17 °FDB
(Outdoor temp.)
Rated
kW 8.10 11.12 12.00
Btu/h 27,600 37,900 40,900
Max.
kW 10.8 12.07 12.48
Btu/h 36,800 41,100 42,500
Input power
Cooling
Rated
kW
3.60 3.65 4.75
Min.—Max. 0.70—4.00 0.75—4.47 0.75—5.01
Heating
47 °FDB
(Outdoor temp.)
Rated 2.88 3.67 4.45
Min.—Max. 0.62—4.38 0.67—4.57 0.67—4.77
17 °FDB
(Outdoor temp.)
Rated 3.29 3.66 4.44
Max. 5.01 4.56 4.76
Fan
HIGH
W
COOL: 158
HEAT: 122
229 248
MED 94 132 146
LOW 59 80 87
QUIET 40 62 66
Current
Cooling
Rated A
15.8 16.0 20.9
Heating 12.6 16.1 19.5
EER Cooling
kW/kW 2.93 3.37 2.96
Btu/hW 10.0 11.5 10.1
COP Heating
kW/kW 3.66 3.75 3.49
Btu/hW 12.5 12.8 11.9
SEER Cooling
Btu/hW
16.7 17.8 16.6
HSPF Heating 11.3 10.5 10.3
Power factor
Cooling
kW/kW
99.1 99.2 98.8
Heating 99.4 99.1 99.2
Moisture removal pints/h (L/h) 5.3 (2.5) 5.5 (2.6) 8.2 (3.9)
Maximum operating current *
1
Cooling
A
17.6 19.7 22.2
Heating 19.1 19.7 20.7
Fan
Airflow rate
Cooling
HIGH
CFM (m
3
/h)
1,207 (2,050) 1,501 (2,550) 1,501 (2,550)
MED 965 (1,640) 1,201 (2,040) 1,201 (2,040)
LOW 783 (1,330) 971 (1,650) 971 (1,650)
QUIET 630 (1,070) 842 (1,430) 842 (1,430)
Heating
HIGH 1,089 (1,850) 1,501 (2,550) 1,501 (2,550)
MED 965 (1,640) 1,201 (2,040) 1,201 (2,040)
LOW 783 (1,330) 971 (1,650) 971 (1,650)
QUIET 630 (1,070) 842 (1,430) 842 (1,430)
Type × Q'ty Sirocco fan × 3
Motor output W 375
Static pressure range Pa 30 to 200 30 to 180
Sound pressure level *
2
Cooling
HIGH
dB (A)
37 40 40
MED 33 35 35
LOW 30 33 33
QUIET 26 29 29
Heating
HIGH 35 40 40
MED 33 35 35
LOW 30 33 33
QUIET 26 29 29
Heat exchanger type
Dimensions (H × W × D) in (mm) 16-9/16 × 45-9/16 × 1-9/16 (420 × 1,158 × 39.9)
Fin pitch FPI 18
Rows × Stages 3 × 20
Pipe type Copper
Fin type
Aluminum
Hydrophilic coating
Enclosure
Material Steel
Color
Dimensions
(H × W × D)
Net
in (mm)
11-13/16 × 55-1/8 × 27-9/16 (300 × 1,400 × 700)
Gross 15-3/4 × 64-1/2 × 34-7/16 (400 × 1,638 × 875)
Weight
Net
lb (kg)
121 (55)
Gross 141 (64)
Connection pipe
Size
Liquid
in (mm)
Ø 3/8 (Ø 9.52)
Gas Ø 5/8 (Ø 15.88)
Method Flare
Drain hose
Material PVC
Size in (mm) Ø 13/16 (20.7) [I.D.], Ø 1-1/16 (26.6) [O.D.] (VP25)
Operation range
Cooling
°F (°C) 64.4 to 89.6 (18 to 32)
%RH 80 or less
Heating °F (°C) 60.8 to 86.0 (16 to 30)
- 6 -
1. Specifications
DUCT TYPE
ARU12-48RGLX
DUCT TYPE
ARU12-48RGLX

Table of Contents

Other manuals for Fujitsu AOU24RGLX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU24RGLX and is the answer not in the manual?

Fujitsu AOU24RGLX Specifications

General IconGeneral
BrandFujitsu
ModelAOU24RGLX
CategoryAir Conditioner
LanguageEnglish

Related product manuals