Operation status
On
On
12 V
Off
Off
0 V
Heater
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone*
Heat pump
prohibition
zone
Heat pump
only zone
Combination zone
*: The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
46.4°F (8°C)
42.8°F (6°C)
-0.F (-18°C)
-4°F (-20°C)
On
Off
Fan
DIP-SW101-3: On
DIP-SW101-3: Off
NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Other than heating
Test run
- 70 -