CASSETTE TYPE
AUU42R
CASSETTE TYPE
AUU42R
- (04 - 27) -
4-15-2. SWITCH FUNCTION (INDOOR UNIT)
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
SW1-1. Auto restart setting
DIP SWITCH SETTING
( Factory setting)
Decide the heating temperature correct coefficient value of heating.
TEMPERATURE CORRECTION
SW1-2, 1-3. Room temperature correct coefficient of heating.
( Factory setting)
SW 1-1
SW state
OFF
Invalidity
ON
Validity
cooling
SW 1-2
SW 1-3
heating
dry
ON
ON
ON
OFF
OFF
OFF
SW state
OFF
ON
SW4-1. Dip SW 4-1setting forbidden
( Factory setting)
SW 4-1
OFF
0 degF
0 degF 0 degF
-3.6degF
0 degF
-3.6degF
-3.6degF+3.6degF
-3.6degF -3.6degF
0 degF
+7.2degF
If the setting for a low ceiling is selected, the capacity of the air
conditioner decreases slightly.
SW4-2, 4-3. Ceiling height setting
( Factory setting)
3
OFF
-
ON
Normal
High ceiling 1
High ceiling 2
Low ceiling
-
ON
ON
-
OFF
-
ON
OFF
OFF
Ceiling height ft. (m)
DIP - SW4
1
2
Less than 8ft. 2-7/16in. (2.5)
9ft. 10-1/8in. to 11ft. 5-25/32in. (3.0 to 3.5)
More than 11ft. 5-25/32in. (3.5)
8ft. 2-7/16in. to 9ft. 10-1/8in. (2.5 to 3.0)

Other manuals for Fujitsu AOU42RLX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU42RLX and is the answer not in the manual?

Fujitsu AOU42RLX Specifications

General IconGeneral
BrandFujitsu
ModelAOU42RLX
CategoryAir Conditioner
LanguageEnglish

Related product manuals