1-2. Outdoor unit
Type Inverter heat pump
Model name AOUG09LZAH1 AOUG12LZAH1 AOUG15LZAH1
Power supply 208/230 V~ 60 Hz
Power supply intake Outdoor unit
Available voltage range 187—253 V
Starting current A 3.3 4.7 5.2
Fan
Airflow rate
Cooling
CFM (m
3
/h)
1,089 (1,850) 1,171 (1,990) 1,218 (2,070)
Heating 1,089 (1,850) 1,089 (1,850) 1,348 (2,290)
Type × Q'ty Propeller fan × 1
Motor output W 49
Sound pressure level *
Cooling
dB (A)
46 47 49
Heating 47 47 50
Heat exchanger type
Dimensions
(H × W × D)
in (mm)
Main 1: 23-1/8 × 34-11/16 × 11/16 (588 × 881 × 18.19)
Main 2: 23-1/8 × 33-1/2 × 11/16 (588 × 851 × 18.19)
Fin pitch FPI 20
Rows × Stages
Main 1: 1 × 28
Main 2: 1 × 28
Pipe type Copper
Fin type
Type (Material) Aluminum
Surface treatment PC fin
Compressor
Type DC rotary
Motor output W 900 1,030
Refrigerant
Type R410A
Charge
lb oz 2 lb 14 oz 2 lb 16 oz
g 1,300 1,350
Refrigerant oil
Type RB68
Amount
in
3
(cm
3
)
24.4 (400)
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
in (mm)
24-7/8 × 31-7/16 × 11-7/16 (632 × 799 × 290)
Gross 27-1/4 × 37 × 14-3/4 (692 × 940 × 375)
Weight
Net
lb (kg)
86 (39) 88 (40)
Gross 95 (43)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø6.35)
Gas Ø3/8 (Ø9.52) Ø1/2 (Ø12.70)
Method Flare
Pre-charge length
ft (m)
49 (15)
Max. length 66 (20)
Max. height difference 49 (15)
Operation range
Cooling
°F (°C)
14 to 115 (-10 to 46)
Heating -15 to 75 (-26 to 24)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80°FDB (26.67°CDB)/67°FWB (19.44°CWB), and outdoor temperature of 95°FDB (35°CDB) /75°FWB (23.9°CWB).
Heating: Indoor temperature of 70°FDB (21.11°CDB)/59°FWB (15°CWB), and outdoor temperature of 47°FDB (8.33°CDB)/43°FWB (6.11°CWB).
Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.