6. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)
6-1. Cooling capacity
Model: ARYG18LHTBP
Model: ARYG24LHTBP
AFR
m
3
/h
1,050
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 3.77 2.98 0.25 4.20 3.00 0.26 4.34 3.26 0.26 4.63 3.27 0.26 4.76 3.54 0.26 5.05 3.52 0.27 5.34 3.75 0.27
-10 3.65 2.93 0.31 4.07 2.95 0.32 4.21 3.20 0.32 4.49 3.21 0.32 4.62 3.47 0.32 4.90 3.45 0.33 5.18 3.68 0.33
0 3.59 2.90 0.34 4.00 2.92 0.35 4.14 3.17 0.35 4.41 3.18 0.35 4.55 3.44 0.35 4.82 3.42 0.36 5.09 3.64 0.36
5 3.47 2.85 0.41 3.86 2.86 0.42 4.00 3.11 0.42 4.26 3.12 0.42 4.39 3.37 0.43 4.65 3.35 0.43 4.92 3.58 0.43
10 3.33 2.78 0.48 3.71 2.79 0.49 3.84 3.04 0.49 4.09 3.04 0.50 4.22 3.29 0.50 4.47 3.28 0.50 4.73 3.49 0.51
15 3.41 2.81 0.40 3.80 2.83 0.41 3.93 3.08 0.41 4.19 3.09 0.41 4.32 3.33 0.41 4.58 3.32 0.42 4.84 3.54 0.42
20 4.41 3.30 0.84 4.91 3.32 0.86 5.08 3.61 0.86 5.41 3.63 0.87 5.58 3.92 0.87 5.91 3.90 0.88 6.25 4.15 0.89
25 4.19 3.19 0.95 4.67 3.21 0.96 4.83 3.49 0.97 5.15 3.51 0.98 5.30 3.78 0.98 5.62 3.77 0.99 5.94 4.02 1.00
30 3.97 3.09 1.05 4.42 3.11 1.07 4.57 3.37 1.07 4.88 3.39 1.08 5.02 3.66 1.09 5.32 3.64 1.10 5.62 3.88 1.11
35 4.11 3.16 1.32 4.58 3.18 1.34 4.73 3.45 1.35 5.04 3.46 1.36 5.20 3.74 1.37 5.51 3.73 1.39 5.82 3.97 1.40
40 3.33 2.78 1.07 3.71 2.80 1.09 3.84 3.04 1.09 4.10 3.04 1.10 4.22 3.29 1.11 4.47 3.28 1.12 4.73 3.49 1.13
46 2.38 2.31 0.82 2.65 2.35 0.83 2.74 2.55 0.83 2.93 2.55 0.84 3.02 2.76 0.84 3.19 2.75 0.85 3.37 2.93 0.86
AFR
m
3
/h
1,360
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 4.92 4.28 0.36 5.49 4.31 0.37 5.67 4.68 0.37 6.05 4.70 0.37 6.23 5.08 0.37 6.61 5.05 0.38 6.98 5.39 0.38
-10 4.78 4.20 0.45 5.32 4.23 0.45 5.50 4.60 0.46 5.87 4.61 0.46 6.04 4.99 0.46 6.41 4.96 0.47 6.77 5.29 0.48
0 4.70 4.17 0.48 5.24 4.19 0.49 5.41 4.55 0.49 5.77 4.57 0.50 5.95 4.93 0.50 6.31 4.91 0.51 6.66 5.23 0.51
5 4.54 4.09 0.59 5.05 4.10 0.60 5.23 4.47 0.60 5.57 4.48 0.60 5.74 4.84 0.61 6.09 4.81 0.61 6.43 5.13 0.62
10 4.36 3.99 0.68 4.85 4.00 0.69 5.02 4.36 0.70 5.35 4.37 0.71 5.52 4.72 0.71 5.85 4.71 0.71 6.18 5.01 0.72
15 4.46 4.04 0.57 4.97 4.07 0.58 5.14 4.42 0.58 5.48 4.43 0.59 5.65 4.79 0.59 5.99 4.77 0.60 6.33 5.08 0.60
20 5.76 4.74 1.20 6.42 4.77 1.22 6.64 5.19 1.23 7.07 5.21 1.24 7.29 5.62 1.24 7.73 5.60 1.26 8.17 5.96 1.27
25 5.48 4.59 1.35 6.10 4.61 1.37 6.32 5.02 1.38 6.73 5.03 1.39 6.94 5.43 1.40 7.35 5.42 1.41 7.77 5.77 1.42
30 5.19 4.43 1.50 5.78 4.46 1.52 5.98 4.84 1.53 6.38 4.86 1.54 6.57 5.25 1.55 6.96 5.22 1.56 7.35 5.57 1.58
35 5.37 4.53 1.88 5.98 4.56 1.91 6.19 4.96 1.92 6.60 4.97 1.94 6.80 5.37 1.95 7.21 5.35 1.97 7.62 5.70 1.99
40 4.36 3.99 1.53 4.85 4.01 1.55 5.02 4.36 1.56 5.36 4.37 1.57 5.52 4.72 1.58 5.85 4.71 1.59 6.18 5.02 1.61
46 3.11 3.32 1.16 3.47 3.37 1.18 3.59 3.66 1.18 3.83 3.67 1.19 3.94 3.97 1.20 4.17 3.95 1.21 4.41 4.20 1.22