- 73 -
OUTDOOR UNIT
AOYG18-54LB
1-2. Models: AOYG30LBTA and AOYG36LBTA
Type
Inverter heat pump
Model name
AOYG30LBTA AOYG36LBTA
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A11.813.4
Fan
Airflow rate
Cooling
m
3
/h
3,600 3,800
Heating 3,600 3,800
Type × Q'ty Propeller × 1
Motor output W 100
Sound pressure level *1
Cooling
dB(A)
53 54
Heating 55 55
Sound power level
Cooling
dB(A)
68 69
Heating 69 70
Heat exchanger type
Dimensions (H × W × D)
mm
798 × 900 × 36.4
Fin pitch 1.3
Rows × Stages 2 × 38
Pipe type Copper
Fin
Type (Material) Corrugate (Aluminum)
Surface treatment Hydrophilic coating (Blue fin)
Compressor
Type × Q'ty Twin rotary × 1
Motor output W 2,100
Refrigerant
Type R410A
Factory charge g 2,100
Refrigerant oil
Type POE (RB68)
Amount
cm
3
800
Enclosure
Material Steel
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0
Dimensions
(H × W × D)
Net
mm
830 × 900 × 330
Gross 970 × 1,050 × 445
Weight
Net
kg
61
Gross 68
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Pre-charge length
m
20
Max. length 50
Max. height difference 30
Operation range
Cooling
°C
-15 to 46
Heating -15 to 24
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.
*1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.