- 74 -
OUTDOOR UNIT
AOYG18-54LB
1-3. Models: AOYG45LBTA and AOYG54LBTA
Type
Inverter heat pump
Model name
AOYG45LBTA AOYG54LBTA
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A15.720.2
Fan
Airflow rate
Cooling
m
3
/h
6,750 6,750
Heating 6,200 6,850
Type × Q'ty Propeller × 2
Motor output W 100 × 2
Sound pressure level *1
Cooling
dB(A)
55 55
Heating 55 57
Sound power level
Cooling
dB(A)
68 69
Heating 68 71
Heat exchanger type
Dimensions (H × W × D)
mm
1,260 × 900 × 36.4
Fin pitch 1.3
Rows × Stages 2 × 60
Pipe type Copper
Fin
Type (Material) Corrugate (Aluminum)
Surface treatment Hydrophilic coating (Blue fin)
Compressor
Type × Q'ty Twin rotary × 1
Motor output W 2,100
Refrigerant
Type R410A
Factory charge g 3,350
Refrigerant oil
Type POE (RB68)
Amount
cm
3
800
Enclosure
Material Steel
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0
Dimensions
(H × W × D)
Net
mm
1,290 × 900 × 330
Gross 1,430 × 1,050 × 445
Weight
Net
kg
86
Gross 94
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Pre-charge length
m
20
Max. length 50
Max. height difference 30
Operation range
Cooling
°C
-15 to 46
Heating -15 to 24
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.
*1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.