14-5. Function details
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Functions
Compact
cassette
Slim duct
Wall
mounted
Floor
1) Filter sign ● ● ● ●
2) Ceiling height ● — — —
3) Outlet directions ● — — —
4) Vertical airflow direction range control — — — ●
5) Static pressure — ● — —
6)
Room temperature control for indoor unit
sensor
● ● ● ●
7) Auto restart ● ● ● ●
8) Room temperature sensor switching ● ● ● ●
9) Remote controller custom code ● ● ● ●
10) External input control ● ● ● ●
11)
Room temperature sensor switching
(Aux.)
● ● ● ●
12)
Indoor unit fan control for energy saving
for cooling
— —
●
ASU7-15RL
F1
●
13)
Room temperature control for wired
remote controller sensor
● ● ●* ●
14)
Heat insulation condition (building
insulation)
● ● ●* ●
*: Exclude ASU7RLF, ASU9RLF, and ASU12RLF.
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
11
00 Standard
01 Long interval
02 Short interval
03 No indication ♦
Intervals will differ depending on the indoor unit type as follows.
Setting description Compact cassette Slim duct Wall mounted Floor
Standard 2,500 hours 400 hours
Long interval 4,400 hours 1,000 hours
Short interval 1,250 hours 200 hours
- 149 -