8. Additional charge calculation
8-1. Model: AOU36RLXFZ1
Refrigerant type R410A
Refrigerant amount
lb oz 7 lb 1 oz
g 3,200
¢ Refrigerant charge
3 or 4 indoor units are connected:
Total pipe length
ft 164 or less 197 230 (Max.)
0.22 oz/ft
(20 g/m)
m 50 or less 60 70 (Max.)
Additional charge
lb oz 0 7.1 oz 14.1 oz
g 0 200 400
2 indoor units are connected (with optional kit K9FZ1818):
Total pipe length
ft 65 or less 98 131 (Max.)
0.27 oz/ft
(25 g/m)
m 20 or less 30 40 (Max.)
Additional charge
lb oz 0 8.9 oz 1 lb 1.8 oz
g 0 250 500
- 303 -
8-1. Model: AOU36RLXFZ1 8. Additional charge calculation
OUTDOOR UNIT
AOU36RLXFZ1
OUTDOOR UNIT
AOU36RLXFZ1

Table of Contents