7. Additional charge calculation
7-1. Models: AOU9RLS3H and AOU12RLS3H
Refrigerant type R410A
Refrigerant amount
lb oz 2 lb 14 oz
g 1,300
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 (Max.)
0.22 oz/ft
(20 g/m)
m 15 or less 20 (Max.)
Additional charge
oz 0 +3.5
g 0 +100
7-2. Model: AOU15RLS3H
Refrigerant type R410A
Refrigerant amount
lb oz 3 lb 1 oz
g 1,400
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 (Max.)
0.22 oz/ft
(20 g/m)
m 15 or less 20 (Max.)
Additional charge
oz 0 +3.5
g 0 +100