02 - 06
-
OUTDOOR UNIT
AOU36R
OUTDOOR UNIT
AOU36R
This table is created using the maximum capacity.
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
INDOOR UNIT 9000BTU (AOU36R)
Height difference H
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is upper than outdoor unit.
1
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is under than outdoor unit.
2
5m 7.5m 10m 15m 20m 25m
16ft. 25ft. 33ft. 49ft. 66ft. 82ft.
15m 49ft. - - -
0.992 0.979 0.963
10m 33ft. - -
0.999 0.992 0.979 0.963
7.5m 25ft. -
1.000 0.999 0.992 0.979 0.963
5m 16ft.
0.999 1.000 0.999 0.992 0.979 0.963
0m 0ft. 0.999 1.000 0.999 0.992 0.979 0.963
-5m -16ft.
0.991 0.992 0.991 0.984 0.972 0.955
-7.5m -25ft. -
0.988 0.987 0.980 0.968 0.951
-10m -33ft. - -
0.983 0.976 0.964 0.947
-15m -49ft. - - -
0.968 0.956 0.940
COOLING
Pipe length
Height difference H
1
2
5m 7.5m 10m 15m 20m 25m
16ft. 25ft. 33ft. 49ft. 66ft. 82ft.
15m 49ft. - - -
0.922 0.900 0.889
10m 33ft. - -
0.962 0.927 0.905 0.893
7.5m 25ft. -
0.993 0.965 0.929 0.907 0.895
5m 16ft.
1.013 0.995 0.967 0.932 0.910 0.898
0m 0ft. 1.018 1.000 0.972 0.936 0.914 0.902
-5m -16ft.
1.018 1.000 0.972 0.936 0.914 0.902
-7.5m -25ft. -
1.000 0.972 0.936 0.914 0.902
-10m -33ft. - -
0.972 0.936 0.914 0.902
-15m -49ft. - - -
0.936 0.914 0.902
HEATING
Height difference H
1
2
Pipe length
5. COEFFICIENT OF COMPENSATION FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
Indoor unit is under
than outdoor unit
Indoor unit is upper
than outdoor unit
Indoor unit is under
than outdoor unit
Indoor unit is upper
than outdoor unit