Operation status
On
On
12 V
Off
Off
0 V
Heater
Fan
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
Heat pump
prohibition
zone
Combination zone
* The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
46.4°F (8°C)
42.8°F (6°C)
-0.4°F (-18°C)
-F (-20°C)
NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Other than heating
Test run
- 37 -
9-4. Details of function 9. External input and output
WALL MOUNTED
ASUG09-15LZAS
WALL MOUNTED
ASUG09-15LZAS