5) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number Setting value Setting description Factory setting
26
00 0 in.WG (0 Pa)
01 0.04 in.WG (10 Pa)
02 0.08 in.WG (20 Pa)
03 0.12 in.WG (30 Pa)
04 0.16 in.WG (40 Pa)
05 0.20 in.WG (50 Pa)
06 0.24 in.WG (60 Pa)
07 0.28 in.WG (70 Pa)
08 0.32 in.WG (80 Pa)
09 0.36 in.WG (90 Pa)
31 Standard (0.10 in.WG [25 Pa]) ♦
NOTE: Range of static pressure is different by model.
Model name Range of static pressure
7-18 type 0 to 0.36 in.WG (0 to 90 Pa)
24 type 0 to 0.20 in.WG (0 to 50 Pa)