Mode
Function
setting
External input
and output
PCB (Rotary
SW)
External output
Indoor unit
Output
External input and output PCB
CN47 Output 1 Output 2 Output 3
0-1 60-00 1 Operation/Stop Operation/Stop Error status
Indoor unit fan
operation status
0-2 60-00 2 Operation/Stop Error status
Indoor unit fan
operation status
External heater
output
1 60-01 3
Cooling
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
2 60-02 4
Cooling
thermostat On
Error status
Remote
controller output
External heater
output
3 60-03 5
Cooling
thermostat On
Cooling high/low
output
Remote
controller output
External heater
output
4 60-04 6
Cooling
thermostat On
Error status
Remote
controller output
Cooling high/low
output
5 60-05 7
Heating
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
6 60-06 8 Operation/Stop Error status
Indoor unit fan
operation status
Heating
thermostat On
7 60-07 9
Cooling
thermostat On
Error status
Heating
thermostat On
External heater
output
8 60-08 A
Cooling
thermostat On
Heating
thermostat On
Remote
controller output
External heater
output
9 60-09 B Error status Operation/Stop
Indoor unit fan
operation status
External heater
output
10 60-10 C
Indoor unit fan
operation status
Operation/Stop Error status
External heater
output
11 60-11 D
External heater
output
Operation/Stop
Indoor unit fan
operation status
Error status
12 60-12 D
Setpoint
Attainment status
Operation/Stop
Indoor unit fan
operation status
Error status
NOTE: Input of Operation/Stop depends on the setting of function setting 46.
00: Operation/Stop mode 1 (Remote controller enabled)
01: (Setting prohibited)
02: Forced stop
03: Operation/Stop mode 2 (Remote controller disabled)
- 90 -
11-3. Combination of external input and output 11. External input and output (Compact cassette type and slim duct type indoor unit)
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type