6-1. Models: AOYA09KLWA and AOYA12KLWA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 10 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
10 — 0.973 0.948 0.936
5 0.995 0.983 0.958 0.945
0 1.000 0.988 0.963 0.950
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.988 0.963 0.950
-10 — 0.988 0.963 0.950
HEATING
Pipe length (m)
5 10 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
10 — 0.993 0.978 0.970
5 1.000 0.993 0.978 0.970
0 1.000 0.993 0.978 0.970
Indoor unit is lower than
outdoor unit *2
-5 0.992 0.985 0.970 0.962
-10 — 0.977 0.962 0.955
- 26 -
6-1. Models: AOYA09KLWA and AOYA12KLWA 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYA09-12KLWA
OUTDOOR UNIT
AOYA09-12KLWA