6. OUTDOOR FAN CONTROL
(1). Fan speed
Outdoor temperature
ASYA24LCC
Heating
1100/1000/730/670/550/450rpm
ASYA30LCC
ASYA24LCC
900/780/700/550/450rpm
Table 6 : Fan speed (Cooling, Dry)
Table 7 : Fan speed (Heating)
The outdoor fan speed is changed in the range of the speed shown in the above table,
based on the frequency of the compressor.
(When the compressor frequency increases, the outdoor fan speed is also changed to
higher speed. If the compressor frequency decreases, the outdoor fan speed is changed
to the lower speed as well.)
After starting up the outdoor fan, it operates with the following speed for initial 20 seconds.
*
Table 8 : Fan speed when starting up Outdoor fan
*
After operating the defrost control function on heating mode, its speed becomes 1,000rpm
regardless of the compressor frequency.
However, it returns to the normal speed control when the defrosting operation does not function
for 240 minutes after releasing the defrost operation or when the outdoor temperature sensor
detection value becomes higher than 5 C.
05-07
Over than 12 C
Less than 12 C
Cooling
950/820/670/500rpm
400/280/230rpm
ASYA30LCC
850/780/700/500rpm
500/320/250/200rpm
Dry
550rpm
400/280/230rpm
550/450rpm
500/320/250/200rpm
Outdoor temperature
ASYA24LCC
Speed
500rpm
200rpm
ASYA30LCC
500rpm
200rpm
Less than 12 C
Over than 12 C
Over than 12 C
Over than 12 C
Less than 12 C
Less than 12 C