19. OFF DEFROST OPEARTION CONTROL
(1). OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation
lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost,
and then stop.
In heating operation, the outdoor heat exchanger temperature is less than - 4 C, and compressor
operation integrating time lasts for more than 30 minutes.
ASYA24LCC
OFF Defrost Flow Chart
Heating operation stop
Defrost end
(2). OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 13 C or
Compressor operation time has passed 15 minutes.
7 sec ON / 2 sec OFF
05-17
ASYA30LCC
Outdoor heat exchanger temperature sensor value is higher than 13 C or
Compressor operation time has passed 15 minutes.