EasyManuals Logo
Home>Fujitsu>Air Conditioner>ASYG07KPCA

Fujitsu ASYG07KPCA User Manual

Fujitsu ASYG07KPCA
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
3) Auto restart
Enables or disables automatic restart after a power interruption.
Function number Setting value Setting description Factory setting
40
00 Enable
01 Disable
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or exter-
nal device.
4) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number Setting value Setting description Factory setting
44
00 A
01 B
02 C
03 D
5) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
49
00 Disable
01 Enable
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
- 21 -
9-1. Function settings by using remote controller 9. Function settings
WALL MOUNTED
ASYG07-12KPCA
WALL MOUNTED
ASYG07-12KPCA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG07KPCA and is the answer not in the manual?

Fujitsu ASYG07KPCA Specifications

General IconGeneral
BrandFujitsu
ModelASYG07KPCA
CategoryAir Conditioner
LanguageEnglish

Related product manuals