6. SYSTEM DESIGN
8) Auto restart
Enable or disable automatic restart after a power interruption.
(
îš¡
... Factory setting)
Setting description Function number Setting value
îš¡
Enable
40
00
Disable 01
*Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external device.
9) Room temperature sensor switching
(Only for Wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
(
îš¡
... Factory setting)
Setting description Function number Setting value
îš¡
Indoor unit
42
00
Both 01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller is active.
*Remote controller sensor must be turned on by using the remote controller.
10) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
(
îš¡
... Factory setting)
Setting description Function number Setting value
îš¡
A
44
00
B 01
C 02
D 03
11) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
îš¡
... Factory setting)
Setting description Function number Setting value
îš¡
Operation/Stop mode
46
00
(Setting prohibited) 01
Forced stop mode 02
12) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
"Wired remote controller" (01). This function will only work if the function setting 42 is set at
"Both" (01)
(
îš¡
... Factory setting)
Setting description Function number Setting value
îš¡
Both
48
00
Wired remote controller 01
- (06 - 86) -