6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Model: AOYG09KHCAN
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.913 0.922
10 0.963 0.928 0.937
7.5 0.980 0.967 0.932 0.941
5 0.992 0.984 0.971 0.936 0.945
0 1.000 0.992 0.979 0.943 0.953
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.992 0.979 0.943 0.953
-7.5 0.992 0.979 0.943 0.953
-10 0.979 0.943 0.953
-15 0.943 0.953
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.990 0.969
10 1.002 0.990 0.969
7.5 1.001 1.002 0.990 0.969
5 1.000 1.001 1.002 0.990 0.969
0 1.000 1.001 1.002 0.990 0.969
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.996 0.997 0.985 0.964
-7.5 0.994 0.995 0.983 0.962
-10 0.992 0.980 0.960
-15 0.970 0.950
- 41 -
6-1. Model: AOYG09KHCAN 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG09-14KHCAN
OUTDOOR UNIT
AOYG09-14KHCAN