- 58 -
OUTDOOR UNIT
AOYG30, 36LMTA
6. Additional charge calculation
6-1. Model: AOYG30LMTA
Refrigerant charge
6-2. Model: AOYG36LMTA
Refrigerant charge
Refrigerant type R410A
Refrigerant amount g 2,100
Total pipe length m 20 or less 30 40 50 (Max.)
40 g/m
Additional charge g 0 400 800 1,200
Refrigerant type R410A
Refrigerant amount g 2,100
Total pipe length m 20 or less 30 40 50 (Max.)
40 g/m
Additional charge g 0 400 800 1,200