- 62 -
OUTDOOR UNIT
AOYG30, 36LMTA
9. Electrical characteristics
*1: Maximum current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate
devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
Model name
AOYG30LMTA AOYG36LMTA
Power supply
Voltage V 230 ~
Frequency Hz 50
Max operating current *1 A 14.5 19.0
Starting current A 10.5 13.9
Wiring spec. *2
Circuit breaker current A 30
Power cable
mm
2
2.5 4.0
Connection cable *3
mm
2
1.5—2.5
Limited wiring length m 51