- 3 -
WALL MOUNTED
ASYG30, 36LMTA
Corresponding to server room air conditioning
Operation:
Cooling operation can be performed even in the low outdoor temperature and low humidity en-
vironment. In addition, the following interlock operation is possible by connecting 2 indoor units
with a cable.
Low ambient operation:
• Alternative operation: 2 units operate alternately.
• Backup operation: In case one unit breaks down, the
other unit starts operation automatically.
• Supporting operation: Both units operate simultane-
ously when the loaded capacity is not enough with one
unit.
• Stable cooling operation is guaranteed down to -15°C
outdoor temperature.
• Keep high sensible cooling performance (approx. 75%
capacity of rated condition) at -15ºC outdoor tempera-
ture. (Room temperature condition: 27°CWB 19°C).
• Server room control can be set at site.
-20
-10
0
10
20
30
40
50
-15
ºC
-15ºC
46ºC
Cooling