- 5 -
WALL MOUNTED
ASYG30, 36LMTA
• Supporting operation
When the room temperature does not reach to the set point after a certain period of time, regard-
less of the primary-secondary relation of the unit, operation start indication is issued to another
unit and both indoor units perform air conditioning simultaneously.
NOTE: While performing this function, following functions cannot be used:
• Operation modes other than cooling
• Airflow modes other than HIGH
• Temperature setting other than 24 °C
• POWERFUL mode
• 10 °C HEAT operation
• ECONOMY operation
• On/off timer, program timer, and SLEEP timer
• Weekly timer on secondary unit
• Human sensor function
• Shutdown operation
• Starting operation on secondary unit
To stop the operation, shutdown the power supply.
On
Indoor unit A
Indoor unit B
Off
On
Off
Set point non-attainment
*: Operaion is started even when the unit is stopped by the weekly timer.
Ts + 0.5 °C
Ts + 2.5 °C
Supporting operation: On
Supporting operation: Off