- (01 - 37) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
1-4. Setting the vertical wind direction adjustment range
•The use of “upward” is recommended if you wish to prevent draft.
(The unit is factory-set to “00”)
•Note that the ceiling may become dirty depending on your usage condition.When this happens,
we recommend the use of the optional “PANEL SPACER KIT”.
(
. . .Factory setting)
Setting Description Function Number Setting Value
Standard
23
00
upward 01
•We recommend the use of “upward” when using “High ceiling mode”.
1-5. Setting the Cooler Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
(
. . .Factory setting)
Setting Description Function Number Setting Value
Standard
30
00
Lower control 01
1-6. Setting the Heater Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be changed as shown in the table below.
(
. . .Factory setting)
Setting Description Function Number Setting Value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
1-7. Auto Restart
The following settings are also possible, depending on the operating conditions.
(
. . .Factory setting)
Setting Description Function Number Setting Value
Yes
40
00
No 01
1-8. Indoor Room Temperature Sensor Switching Function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature
sensor.
(
. . .Factory setting)
Setting Description Function Number Setting Value
No
42
00
Yes 01
If setting value is “00”,
•
room temperature is controlled by the indoor unit temperature sensor.
If setting value is “01”,
•
room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.