Figure 19 Unit Installation Area
ETERNUS AF
(1)
(2)
(3)
(4)
Rear door of the rackFront door of the rack Rack pillars
Rack rails
Table 20 Specifications for the Unit Installation Area
Specification Condition
(1) Rack front space
(Space between the fixed part of the
ETERNUS AF on the
front side and the front of the rack)
40mm or more
(2) Mount bracket length
(Size between each end of the front and rear rack pillars)
685mm or more
775mm or less
(3) Rack space
(Space between the fixed part of the
ETERNUS AF on the
front side and the rear of the rack)
830mm or more
(4) Rack mount kit installation area 482mm or more
(recommended)
■
Placement Requirements
When determining service areas, refer to the manual of the rack that is to be used.
Make sure to perform the installation according to the placement requirements described in "
Installation Specifi-
cations" (page 7) and "Installation Environment" (page 16).
2. Rack Installation Specifications
Installable Racks
36
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AG-1812-06ENZ0