En-11
(... Factory setting)
Setting description
Function
number
Setting value
Standard
30
00
Slightly lower control 01
Lower control 02
Warmer control 03
(4) Heating room temperature correction
Depending on the installed environment, the room temperature sensor
may require a cor-
rection.
The settings may be changed as shown in the table below.
(... Factory setting)
Setting description
Function
number
Setting value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
(5) Auto restart
Enable or disable automatic system restart after a power outage.
(... Factory setting)
Setting description
Function
number
Setting value
Yes
40
00
No 01
* Auto restart is an emergency function such as for power failure etc. Do not start and stop
the indoor unit by this function in normal operation. Be sure to operate by the control unit,
or external input device.
(6) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when using the Wired remote controller temperature
sensor.
(... Factory setting)
Setting description
Function
number
Setting value
No
42
00
Yes 01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote
controller unit sensor.
(7) Wireless remote controller signal code
Change the indoor unit Signal Code, depending on the wireless remote controllers.
(... Factory setting)
Setting description
Function
number
Setting value
A
44
00
B01
C02
D03
(8) External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(... Factory setting)
Setting description
Function
number
Setting value
Operation/Stop mode
46
00
(Setting forbidden) 01
Forced stop mode 02
Setting record
Record any changes to the settings in the following table.
Setting Setting Value
(1) Filter sign
(2) Static pressure
(3) Cooling room temperature correction
(4) Heating room temperature correction
(5) Auto restart
(6) Indoor room temperature sensor switching func-
tion
(7) Wireless remote controller signal code
(8) External input control
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
SETTING THE ROOM TEMPERATURE DETECTION
LOCATION
The detection location of the room temperature can be selected from the following 2 examples.
Choose the detection location that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature sensor
.
(1) When the THERMO SENSOR button is pressed, the lock display ashes because the
function is locked at the factory.
A
Indoor unit
B. Indoor unit/remote controller setting (room tempera-
ture sensor selection)
The temperature sensor of the indoor unit or the remote controller can be used to detect
the room temperature.
(1) Enable the room temperature sensor selection in FUNCTION SETTING, which will be
previous page.
(2) Press the THERMO SENSOR button for 5 seconds or more to select the temperature
sensor of the indoor unit or the remote controller.
B