Check point 3. Check the solenoid coil and 4-way valve
NOTE: Refer solenoid coil and 4-way valve in "Service parts information" on page 03-37.
Solenoid coil
Remove P60 from PCB and check the resistance value of coil. Resistance value is 1.88 kΩ —
2.29 kΩ (at 20 °C).
→ If it is open or abnormal resistance value, replace solenoid coil.
4-way valve
Check each piping temperature, and the location of the valve by the temperature difference.
If the value location is not proper, replace 4-way valve.
Check point 4. Replace main PCB
If Check Point 1 to 4 do not improve the symptom, replace main PCB.
End
2-22. E: 99. 4-way valve error (Outdoor unit) - (03-27) - 2. Troubleshooting with error code