1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Model name Outdoor temperature zone
Limitation of compressor
frequency
ROG09KMCDN
A zone 38 rps
B zone 38 rps
C zone 36 rps
D zone 31 rps
E zone 1 rps
F zone 30 rps
ROG12KMCDN
A zone 34 rps
B zone 34 rps
C zone 34 rps
D zone 34 rps
E zone 12 rps
F zone 18 rps
ROG14KMCDN
A zone 32 rps
B zone 32 rps
C zone 32 rps
D zone 32 rps
E zone 14 rps
F zone 22 rps
1-5. Compressor frequency limitation by outdoor temperature - (04-6) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS