1. Compressor frequency control
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
frequency of the compressor.
If the room temperature is 6.0 °C higher than a set temperature, the compressor operation fre-
quency will attain to maximum performance.
If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +6.0°C to -1.0°C of the setting temperature, the
compressor frequency is controlled within the range shown in the table below. However, the maxi-
mum frequency is limited in the range shown in the figure below based on the indoor fan mode
and the outdoor temperature.
Compressor frequency range
Model name Minimum frequency Maximum frequency
RSG09KMCDN
RSG12KMCDN
8 rps 63 rps
RSG14KMCDN 10 rps 58 rps
1-1. Cooling operation - (04-1) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS